Dell UPS 1920T Bedienungsanleitung Seite 75

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 88
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 74
75
MIB Objects
|
Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path Trap LevelTrap
trapBatteryTestDone (physical BatteryTestStatus)
Battery test done
Variable: physicalBatteryTestStatusUPS.BatterySystem.Battery.Test ? 5
62 1
trapBatteryNeedReplacement
Battery test failed, battery needs to be replaced
UPS.PowerSummary.PresentStatus.NeedReplacement = 1
63 3
trapBatteryReplacementDone
Battery replacement done
UPS.PowerSummary.PresentStatus.NeedReplacement = 0
64 1
trapFanFailure
Fan failure
UPS.PowerSummary.PresentStatus.FanFailure = 1
65 3
trapFanOk
Fan ok
UPS.PowerSummary.PresentStatus.FanFailure = 0
66 1
trapSiteWiringFault
Site wiring fault
UPS.PowerConverter.Input[1].PresentStatus.WiringFault = 1
67 3
trapSiteWiringOk
Site wiring ok
UPS.PowerConverter.Input[1].PresentStatus.WiringFault = 0
68 1
trapBatteryDisconnected
Batteries disconnected
UPS.BatterySystem.Battery.PresentStatus.Present = 0
69 3
trapBatteryConnected
Batteries connected
UPS.BatterySystem.Battery.PresentStatus.Present = 1
70 1
trapUPSOff
UPS off
UPS.PowerSummary.PresentStatus.Good = 0
71 2
trapUPSOn
UPS on
UPS.PowerSummary.PresentStatus.Good = 1
72 2
Seitenansicht 74
1 2 ... 70 71 72 73 74 75 76 77 78 79 80 ... 87 88

Kommentare zu diesen Handbüchern

Keine Kommentare