MIB Objects
Table 15. Product Physical Group Variables (continued)
Trap Name, Description, and Relative XML Object Path Trap LevelTrap
trapPosDCLinkUnderVoltage
Positive DC link under voltage (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.LowPositiveDCBusVoltage = 1
27 2
trapPosDCLinkUnderVoltageOk
Positive DC link under voltage ok
UPS.PowerConverter.Rectifier.PresentStatus.LowPositiveDCBusVoltage = 0
28 1
trapNegDCLinkOverVoltage
Negative DC link over voltage (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.HighNegativeDCBusVoltage = 1
29 2
trapNegDCLinkOverVoltageOk
Negative DC link over voltage ok
UPS.PowerConverter.Rectifier.PresentStatus.HighNegativeDCBusVoltage = 0
30 1
trapNegDCLinkUnderVoltage
Negative DC link under voltage (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.LowNegativeDCBusVoltage = 1
31 2
trapNegDCLinkUnderVoltageOk
Negative DC link under voltage ok
UPS.PowerConverter.Rectifier.PresentStatus.LowNegativeDCBusVoltage = 0
32 1
trapRectifierFault
Rectifier fault (applies only to double-conversion models)
UPS.PowerConverter.Rectifier.PresentStatus.InternalFailure = 1
33 3
trapRectifierOk
Rectifier ok
UPS.PowerConverter.Rectifier.PresentStatus.InternalFailure = 0
34 1
trapInverterFault
Inverter fault (applies only to double-conversion models)
UPS.PowerConverter.Inverter.PresentStatus.InternalFailure = 1
35 3
trapInverterOk
Inverter ok
UPS.PowerConverter.Inverter.PresentStatus.InternalFailure = 0
36 1
trapChargerFailure
Charger failure
UPS.BatterySystem.Charger.PresentStatus.InternalFailure = 1
37 3