About Your Solution 25
E1311 Fan module ##
RPM exceeding
range. Check
fan.
RPM of specified fan in
specified module is
outside of intended
operating range.
See "Troubleshooting
System Cooling
Problems" on page 96.
E1313 Fan redundancy
lost. Check
fans.
The system is no longer
fan redundant. Another
fan failure would put the
system at risk of
over-heating.
Check LCD for
additional scrolling
messages. See
"Troubleshooting a Fan"
on page 97.
E1410 Internal Error
detected.
Check "FRU X".
Specified processor has an
internal error. The error
may or may not have been
caused by the processor.
Remove AC power to the
system for 10 seconds and
restart the system.
If the problem persists,
see "Getting Help" on
page 113.
E1414 CPU # temp
exceeding
range. Check
CPU heatsink.
Specified processor is out
of acceptable temperature
range.
Ensure that the processor
heat sink is properly
installed. See
"Troubleshooting the
Processor" on page 102
and "Troubleshooting
System Cooling
Problems" on page 96.
E1418 CPU # not
detected.
Check CPU is
seated
properly.
Specified processor is
missing or bad, and the
system is in an
unsupported
configuration.
Ensure that the specified
microprocessor is
properly installed. See
"Troubleshooting the
Processor" on page 102.
E141C Unsupported
CPU
configuration.
Check CPU or
BIOS revision.
Processor is in an
unsupported
configuration.
Ensure that your
processor matches and
conforms to the type
described in the processor
technical specifications
outlined in your system’s
Getting Started Guide.
Table 1-3. LCD Status Messages
(continued)
Code Text Causes Corrective Actions
book.book Page 25 Monday, January 24, 2011 12:24 PM