Upgrading UPS Firmware
3 Choose one of the following communication methods through which to upgrade the UPS
firmware (see Figure 14):
S Select RS232 or USB to use the PC COM port or USB port to upgrade locally.
S Select NMC to use the Dell Network Management Card Ethernet interface to upgrade over
the network.
Figure 14. Selecting the Communication Method
4 NMC option only. Enter the IP address of the Dell Network Management Card, and either enter
the SNMP Read Community value or accept the default value (public).
NOTE:
Unless SNMP is enabled, you cannot use the Dell Network Management Card as an Ethernet interface
to upgrade the UPS.
5 Complete the User and Password fields.
Seitenansicht 21