Dell UPS 10000R Bedienungsanleitung Seite 20

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 244
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 19
18
|
Installation and Startup
Hardwiring the UPS Input
WARNING:
Risk of electrical shock. Only qualified service personnel (such as a licensed electrician) shall
perform the electrical installation.
The Dell Online Rack hardwired models require a dedicated branch circuit that meets the following
requirements:
S
Protection device requires a two-pole disconnection device between the UPS input and the mains
S
Breaker must be wall-mounted and be readily accessible to the operator
S
For Europe. Breaker must meet the IEC/EN 60934 standard and at least 3 mm contact air gap
S
200–240 Vac
S
Single-phase
S
50/60 Hz
S
Flexible metal conduit (recommended for ease of service and maintenance)
AC Mains
Wall
2-pole
Breaker
UPS
Line
Neutral/L2
Seitenansicht 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 243 244

Kommentare zu diesen Handbüchern

Keine Kommentare