2 Dell Metered Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Metered Rack PDU distributes power to the devices in the rack.
OUTLETS. The Rack PDU has twenty-one (21) IEC-320-C13 outlets and six (6) IEC-320-C19 outlets.
P
OWER CORD. The Rack PDU has an IEC-320-C20 inlet and can be used with a detachable power cord (not provided).
K535N
Electrical
Input connection IEC-320-C20
Acceptable input voltage 100–240 VAC +6%, -10%
Maximum input current (phase) 16 A
Input frequency 50/60 Hz
Input power 3.8 kVA UL and C-UL (derated), PSE, International
Output voltage 100–120 VAC (Line-to-Neutral)
Output connections Twenty-one (21) IEC-320-C13; Six (6) IEC-320-C19
Maximum output current (outlet) IEC-320-C13: 12 A; IEC-320-C19: 16 A UL and C-UL
(derated), PSE
IEC-320-C13: 10 A; IEC-320-C19: 16 A International
Maximum output current (phase) 16 A UL and C-UL (derated), PSE, International
Physical
Dimensions
(H x W x D)
162.5 x 5.5 x 4.6 cm
(64.0 x 2.2 x 1.7 in)
Shipping dimensions
(H x W x D)
187.5 x 22.6 x 13.5 cm
(73.8 x 8.9 x 5.3 in)
Weight 3.9 kg (8.5 lb)
Shipping weight 5.7 kg (12.5 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing